Refrigeration Systems of Evansville (RSE) was founded in 1973 by two engineers working from a converted service station. From this beginning, the company grew steadily; and in 1989, it merged with Evansville Metal Products  - a move which doubled sales and greatly expanded the company' s product lines.

Today RSE has become a foremost manufacturer of commercial, industrial, and residential refrigeration products in the nation. Using only the highest quality name-brand components, RSE produces a full line of packaged refrigeration systems and heat transfer equipment, including:
 

CHILLER-EVAPORATORS, shell and tube evaporators for cooling fluids and gases.




Since its inception, Refrigeration Systems of Evansville has been dedicated to manufacturing reliable products that are unsurpassed in quality and that can be sold at a competitive price. We continue to achieve these goals by meeting our customers' needs through continuous improvement in the quality of our people, products, and services.

Our quality policy embraces a number of key principles
that are at work throughout our organization

Customer Satisfaction:  Ultimately, quality is measured by our ability to meet - and exceed - our customers' expectations. Customers are the final judge of quality. This is why our customers remain the focus of everything we do at RSE.

Continuous Improvement:  Because quality requirements are constantly changing, we remain committed to continuous improvement in every aspect of our operation.

People:  By far, the most valuable resource at RSE is our people, an experienced, highly skilled team of engineers, technicians, and managers. They are well trained, involved, and individually committed to outstanding product quality and customer service.

Products:  In each step of the production process, we emphasize quality control. The result is a quality product, manufactured to meet or surpass all functional and aesthetic requirements.

Consistency:  By minimizing variability in our processes, we are able to build quality into all of our products - and do so consistently.

Service:  Our products are supported by service that responds to our customers' needs. This involves on-time delivery, after-sale support, and regular communication with our customers on quality issues.



Low Side Chiller Package - SINGLE Circuit Components




Low Side Chiller Package - DUAL Circuit Components




Low Side Chiller Package - MULTIPLE Circuit Components



COMPONENTS:
The FXLG includes a Model FX chiller barrel with 3/4" Armaflex insulation, thermostatic expansion valve(s), liquid solenoid valve(s) (120 volt), moisture indicating sight glass(es), flow switch and a control box housing the temperature control, freezestat, 24 volt transformer and control circuit breaker.

WARRANTY:
RSE low side chiller barrels include a:  One year warranty on parts and service.
 

All of our products use the highest quality materials with state of the art craftsmanship.  If you are looking for a new or used, refurbished, repaired, or a replacement chiller barrel - contact Refrigeration Systems of Evansville for a competitive price quote on a new FXLG unit.

 





 

ENGINEERED SPECIFICATIONS

SHELL - made of steel pipe, ASME Spedfications SA-53B/SA-106-B. Shells are chemically cleaned before assembly.

TUBE SHEETS - are flanged carbon steel, ASME Specifications SA-285 (Grade C) or SA-516-70.

BAFFLES - die punched non-corrosive polypropylene plastic.

TUBES - Seamless copper, 5/ B" O.D., ASME Specification SB-75, and fitted with a live point, notched spiral aluminum insert.

GASKETS - Die-cut in conformance with relevant specifications. Vessels are pneumatically tested for leaks.

CONNECTIONS - Shell side connections 3" and smaller are of ASA forged fittings. Connections larger than B" will terminate in 150 lb. ASA Steel flanges. Thermowell and drain connections will be provided.

REFRIGERANT CONNECTIONS AND EXTRA HEAVY PIPE (FPT TYPE) - Welded to the head and bored to accept the O. D. of copper tubing.

CODES & WORKING PRESSURES - Constructed in accordance with Section VIII Div. 1 of the ASME code for pressure vessels and stamped accordingly.

SHELL (FLUID) SIDE WORKING PRESSURE  = 150 PSI @ 200°F.

TUBE (REFRIGERANT) SIDE WORKING PRESSURE  = 225 PSI @ 300°F.

FINISH - All exterior surfaces will be painted with shop primer and insulated with 3/4" closed cellular insulation.

OPTIONS - Saddles: Fabricated steel saddle type supports to fit the outside diameter of the cooler.

LIQUID LINE GROUP - Includes thermostatic expansion valve(s) with external equalizer, liquid line solenoid valve(s) (120 volt), moisture indicating sight glass(es). Components are mounted, piped, and leak tested with dry nitrogen. Held connections are stubbed in copper for easy field connections.

ELECTRICAL CONTROL GROUP - Includes flow switch, temperature control with staging for each circuit, low temperature cut out, circuit breaker, 24 volt transformer to power the condensing unit contractor coil.

QUALITY CONTROL - The entire vessel will be thoroughly inspected and tested ensuring conformance to engineering specifications prior to shipping.



 